TECHNOLOGY INFRASTRUCTURE
What options are available for hosting a mission-critical system?
For more information about colocation, please contact us at 877.CTG.1300 or email us at moreinfo@catalysttg.com.
|
Colocation
To accommodate high availability websites, critical Internet -connected servers, and virtual office organizations, Catalyst offers collocation and managed services to our clients. Catalyst offers two collocation sites. One is located in downtown Indianapolis and the second in downtown Chicago. Our customers receive key card access to the facilities and we also offer remote access to your systems at both locations.
Security & Access:
- 24/7 security management via the Security Operations Center (SOC)
- Remote camera monitoring 24/7, backed by digital recordings on file for 45 days
- Access to equipment area 24/7 days via card key and pass code only
- Locking cabinets
- Full CCTV surveillance
Power Infrastructure:
- 1,000 to 1,600 amps at 480 volt total capacity, depending on site
- 80 to 85 watts per square foot including HVAC
- 120/208V AC and -48V DC available
- 100% generator backup
- Generator capacity 600-2000 KW
- Size of fuel tank 1,000 to 2,000 gallons
- Generator both auto start and auto transfer. Isolation bypass feature on automatic transfer switch
- Minimum 24-hour run time fuel capacity; Two-hour response for fuel delivery
- UPS backup power
- Voltage output 480 transformed to 120/208 V
- -48 Volt DC Battery Plant
- 1200 amp expandable to 4800 amp
- 2-hour battery reserve non-redundant, 4 hours redundant
- "True" A/B power feeds
- Grounding in accordance with NFPA 70
Environmental Controls:
- Under-floor cooling provided by computer-room grade equipment
- Cooling not less than 150 BTU/h per square foot with an N+1 redundancy
- Temperature is maintained at 72 degrees F dry bulb at ASHRAE 1%
- In the event of a power interruption HVAC systems (and entire facility) operate on diesel generators
- 30% to 60% humidity non-condensing. Humidity control delivered through ATS/Liebert units via infra-red humidifier
- Top-quality, electrostatic dissipative raised floor tiles designed for 100 psf, and in some facilities 250 lbs. psf, floor load
Fire Detection & Suppression:
- Pre-action sprinkler rated for telecommunication equipment/computer room
- Integrated smoke/heat detector system
- Under-floor leak detection system
Partners:
What Catalyst Supports:
- Rack space starting at just 1U
- Pre-built rack infrastructure (KVM, monitor, UPS power, etc.)
- High speed Internet access speeds starting at 256Kbps up to 45Mbps
- Ethernet Internet handoff
- Colo Managed Shared Firewall Service
- Colo Managed Dedicated Firewall Service
- Colo Managed Server Service
- Colo Managed Backup Service
- Colo Managed Site-to-Site VPN Service
- Colo Managed VPN User Service
Related Service Offerings:
Servers | Desktops | Security | Networking | E-mail | Collaboration | Remote Access | Hosting | Colocation | Backup/D.R. | Software/Licensing
|